Hongchun Shu1,2, Yaqi Deng1,2,*, Pulin Cao2, Jun Dong2, Hongjiang Rao2, Zhiqian Bo2
Energy Engineering, Vol.119, No.2, pp. 523-538, 2022, DOI:10.32604/ee.2022.015570
- 24 January 2022
Abstract The arc-suppression coil (ASC) in parallel low resistance (LR) multi-mode grounding is adopted in the mountain wind farm to cope with the phenomenon that is misoperation or refusal of zero-sequence protection in LR grounding wind farm. If the fault disappears before LR is put into the system, it is judged as an instantaneous fault; while the fault does not disappear after LR is put into the system, it is judged as a permanent fault; the single-phase grounding fault (SLG) protection criterion based on zero-sequence power variation is proposed to identify the instantaneous-permanent fault. Firstly, the More >