First and Second Law Analysis of a LiBr-Water Absorption Cycle with Recovering Condensation Heat for Generation

by J. L. Rodríguez-Muñoz1,*, J. S. Pacheco-Cedeño1,*, J. F. Ituna-Yudonago2, J. J. Ramírez-Minguela3, I. J. González-Hernández4

1 Department of Mechanical Engineering, Escuela Superior de Ciudad Sahagún, Universidad Autónoma del Estado de Hidalgo, Ciudad Sahagún, Carretera Cd. Sahagún-Otumba s/n, Zona Industrial, Hidalgo, C.P. 43998, México
2 Departamento de Ingeniería en Aeronáutica, Universidad Politécnica Metropolitana de Hidalgo, Boulevard Acceso a Tolcayuca 1009, Ex Hacienda de San Javier Tolcayuca, Hidalgo, C.P. 43860, México
3 Department of Chemical Engineering, University of Guanajuato, DCNE, Col. Noria Alta s/n, Guanajuato, Gto., C.P. 36050, México
4 Department of Industrial Engineering, Escuela Superior de Ciudad Sahagún, Universidad Autónoma del Estado de Hidalgo, Ciudad Sahagún, Hidalgo, C.P. 43998, México

* Corresponding Authors: J. L. Rodríguez-Muñoz. Email: email; J. S. Pacheco-Cedeño. Email: email

(This article belongs to the Special Issue: Modeling, Control, and Optimization of Energy Modules and Systems)

Frontiers in Heat and Mass Transfer 2024, 22(6), 1719-1741. https://doi.org/10.32604/fhmt.2024.057924

Abstract

In conventional absorption refrigeration systems (ARS), the heat from the condenser is usually rejected by the environment in place to be used in the system, so recuperating this is a good alternative to enhance the system’s performance. For instance, in this paper, an alternative ARS in which LiBr/Water is used as a refrigerant mixture, where part of condensing heat is recovered via the solution heat recovery generator absorption cycle (HR-ARS) was energy and exergy evaluated. The influence of generator, condenser and evaporator temperatures, as well as the efficiency of the solution heat exchanger on the coefficient of performance, exergy performance and exergy destroyed of the HR-ARS system, were analyzed and compared with the traditional ARS system at the same working conditions. The results showed an increase between 5.8%–6.3% on the COP and 3.7%–9.5% in the exergy efficiency when condenser/absorber temperature was reduced from 40°C to 30°C. However, when the evaporation temperature rose from 5°C to 15°C, the COP (coefficient of performance) increased by around 8%, although this could be increased by 2.3%–6.3% if the generator temperature decreases from 100°C to 80°C. Moreover, the COP and exergetic performance for the HR-ARS is more significant at the lowest generator, condenser and evaporator temperatures, as well as at high efficiency in the solution heat exchanger, in comparison to ARS system. Furthermore, the COP and exergy performance for the HR-ARS system was improved by 2.57% to 3.11% and 0.22% to 0.7%, respectively, while the recovering condensation heat for generation is around 1.51%–3.76% lower than with the ARS. It also was found that for all ranges of evaporator and condenser temperatures, the COP for the HR-ARS system is around 3% higher than that obtained with the ARS at the three different generator temperatures here analyzed, while when the solution heat exchanger effectiveness was increased from 0.7–1.0, the total exergy destruction for the HR-ARS resulted be 3.24%–5.01% smaller than the ARS system. Finally, it can be concluded that the components with the most exergy destroyed in the systems (80% to 94%) are the generator and absorber.

Graphic Abstract

First and Second Law Analysis of a LiBr-Water Absorption Cycle with Recovering Condensation Heat for Generation

Keywords


Cite This Article

APA Style
Rodríguez-Muñoz, J.L., Pacheco-Cedeño, J.S., Ituna-Yudonago, J.F., Ramírez-Minguela, J.J., González-Hernández, I.J. (2024). First and second law analysis of a libr-water absorption cycle with recovering condensation heat for generation. Frontiers in Heat and Mass Transfer, 22(6), 1719-1741. https://doi.org/10.32604/fhmt.2024.057924
Vancouver Style
Rodríguez-Muñoz JL, Pacheco-Cedeño JS, Ituna-Yudonago JF, Ramírez-Minguela JJ, González-Hernández IJ. First and second law analysis of a libr-water absorption cycle with recovering condensation heat for generation. Front Heat Mass Transf. 2024;22(6):1719-1741 https://doi.org/10.32604/fhmt.2024.057924
IEEE Style
J. L. Rodríguez-Muñoz, J. S. Pacheco-Cedeño, J. F. Ituna-Yudonago, J. J. Ramírez-Minguela, and I. J. González-Hernández, “First and Second Law Analysis of a LiBr-Water Absorption Cycle with Recovering Condensation Heat for Generation,” Front. Heat Mass Transf., vol. 22, no. 6, pp. 1719-1741, 2024. https://doi.org/10.32604/fhmt.2024.057924



cc Copyright © 2024 The Author(s). Published by Tech Science Press.
This work is licensed under a Creative Commons Attribution 4.0 International License , which permits unrestricted use, distribution, and reproduction in any medium, provided the original work is properly cited.
  • 306

    View

  • 71

    Download

  • 0

    Like

Share Link