Dynamic Characteristics Analysis of Ice-Adhesion Transmission Tower-Line System under Effect of Wind-Induced Ice Shedding
Yongping Yu1, Lihui Chen1, Juanjuan Wang1, Guoji Liu2,*
1 College of Construction Engineering, Jilin University, Changchun, 130021, China
2 College of Physics, Jilin University, Changchun, 130012, China
* Corresponding Author: Guoji Liu. Email:
Computer Modeling in Engineering & Sciences 2020, 125(2), 647-670. https://doi.org/10.32604/cmes.2020.011067
Received 17 April 2020; Accepted 10 August 2020; Issue published 12 October 2020
Abstract
The tower line system will be in an unsafe status due to uniform or
uneven fall of ice coating which is attached to the surface of tower and lines.
The fall of ice could be caused by wind action or thermal force. In order to
study the dynamic characteristics of the self-failure of the transmission line
under the action of dynamic wind load, a finite element model of the two-span
transmission tower line system was established. The birth and death element
methods are used to simulate the icing and shedding of the line. Tensile failure
strength is the shedding criterion for ice coating. The fluctuating wind speed
time history of the tower line system is first simulated, and then the fluctuating
wind and the average wind are superimposed to generate the instantaneous
wind speed and converted into wind load. The dynamic response of the
transmission tower line system under iced coupling with different wind speeds
and different thicknesses of ice coating was studied. This is the first attempt
that the coupling dynamic response of the icing shedding and wind load for
the transmission tower-line system is discussed in this paper. In addition,
the dynamic characteristics of wind are included. In particular, the limiting
mechanical conditions are considered. According to the simulation results,
it is found: because of the ice shedding, the stress of the conductor changes
obviously in the first 20 seconds, and the ground wire changes sharply in the
first two seconds; the icing of the conductor (ground) wire is gradually deicing
under the action of wind vibration; the displacement of tower top increases
with the increase of wind speed and icing thickness.